Central Heating system Repair
The client reported an issue with the heating system not functioning properly. Upon inspecting the furnace in the basement, I found that the spark ignition cable was disconnected, preventing the heating system from igniting. It appears that another service technician had recently replaced the fan motor and may have forgotten to reconnect the ignition wire after disconnecting the control board.
Additionally, I found a 20 microfarad capacitor simply lying at the bottom of the furnace. If that capacitor were to fall due to the suction from the fan motor, it could potentially surge the entire unit, damaging the control board and possibly causing severe electrical issues. Furthermore, the wiring from the new fan motor was completely loose and could have been sucked into the fan wheel, creating an electrical short.
I reconnected the spark ignition wire to its proper location and turned the system on. The heat started functioning correctly. I also created a bracket for the new capacitor and secured the wiring with zip ties. After testing the system again, it operated properly and was good to go.

A/C Tune Up
Client had a problem with the HVAC system, not working properly, upon arrival we found the system completely froze up with ice, what’s the ice melt We found a problem with the air filter. Also, the outdoor condenser unit needed to be washed. The coil was extremely dirty.

Tune Up Central A/C System
Service the entire HVAC system in two zones, install two traps with sensors, and charge the first floor system with refrigerant

Service Tune up mini split
Service tune-up of the ductless mini-split system.

Service Hot air furnace and install media Cleaner
Deep cleaning of the furnace. Combustion analysis. Wiring adjustment. Electrical components cleaning. Installation of media cleaner and bypass humidifier

Furnace Tune Up service
High-efficiency furnace maintenance. Clean burner tubes. Change filters. Clean the condensation drain line. Evaluate combustion. Ensure the furnace is good for winter.

Hot Air furnace Tune Up
Furnace maintenance. Cleaning of the furnace. Filter change. Overall inspection of operations.

Hot Air Furnace Tune Up
High-efficiency furnace maintenance. Cleaning of the combustion chamber. Inspection of overall operation of the furnace

Hot Air Furnace Tune Up
Performed hot air furnace maintenance. High-efficiency furnaces. Cleared condensation traps. Cleaned burner tubes with nitrogen. Cleaned electronics with a soft-bristled brush. Tested the gas valve operation.

Steam Boiler Tune Up
Steam + AC and hot water. Started by having the owner turn on both systems to confirm they were working. Both boilers turned on normally. Shut the systems off using the emergency service switch. Flushed boilers. Cleaned externals and combustion chambers. Applied rust prevention. Turned both systems on and checked radiators.

Heating Tune Up
Performed tune-up. Started the basement furnace. Turned system on from thermostat. System was already set to heat at 70°. Furnace started up normally. Shut system off using emergency service switch. Cleaned flame sensor. Hot surface ignitor glowing bright red and hot. Furnace is working well and ready for winter.

Central A/C Repair + Tune-Up
We performed a tune-up for the basement and attic units. We replaced the capacitor for the 2nd-floor unit; the existing one was defective. We checked both units, and everything is working properly.

Central A/C Tune Up
A/C tune-up: Turned systems on from the thermostats. 3 systems total. Went outside to confirm all condensers turned on. All systems working. Removed cover and cleaned inside the condenser. All systems are working well and are ready for summer.

A/C Tune-Up + Repair
The client called to report a problem with the central air-conditioning system not working.
Upon arrival, we turned the system on and observed the outdoor condenser. The compressor will turn on, but the fan would not.
When we checked the condenser capacitor, we found that the fan side of the capacitor had blown out. Fortunately, it’s beyond repair. A new capacitor is needed. Once we installed the new capacitor, we had a chance to assess the overall functionality of the system and determine that the refrigerant levels are within the proper range.
The unit is achieving an 18° differential; however, the air coming out of the condenser is extremely hot. This is due to the fact that the condenser radiator coil is very dirty internally and needed to be power washed with heavy degreaser.
With the client’s permission, we began servicing the condenser unit. We vacuumed all debris from inside the condenser, power washed the bottom and the coil several times to remove all dirt buildup, then used a brush to clean all electrical components and blew them dry with an air gun.
Inside the house, we discovered that the conversation trap had no access for cleaning. With the client’s permission, we installed a T connection, then found that the trap was clogged. If not addressed, this could lead to a conversation leak.
At this point, everything is ready to go. The system is fully cleaned and operating well.
One-year limited warranty on parts and labor for the capacitor.